
Highly functional IO-Link Master for various industrial Ethernet
Mixed connection of digital Sink(NPN) / Source(PNP) I/O devices is realized with one unit.
- A single unit to connect digital Sink(NPN) and Source(PNP) I/O devices
A single unit to connect digital Sink(NPN) and Source(PNP) I/O devices.
Not only IO-Link devices, but also digital Sink(NPN) / Source(PNP) I/O devices can be connected Together in one unit.
- 16 channels
Connects to more than twice as many I/O devices as standard IO-Link Master.
Save costs and space.
- Realized the minimum cycle time of 0.3 ms
The IO-Link minimum cycle time achieves the industry's fastest* high-speed response of 0.3 ms.
The response time issue of IO-Link communication has been resolved.
- Realization of palm size
Approx. 1/2 the size (W110 x D31.4 x H63 mm) of a standard IO-Link Master (8 channels).
In addition, the number of channels is doubled, which contributes to space saving in the equipment.
*In IO-Link Master with display and operation unit.
Surveyed by OPTEX FA in November, 2021.
- 10 languages supported
Ten languages can be easily selected in the system menu.
The global design allows for safe and reliable use even when equipment is moved overseas.
- Automatic IODD download function
Using IO-Link Master and IO-Link devices of OPTEX FA eliminates the need to configure IODD files.
- Supports 7 field networks
The multi-protocol design of this unit can be easily switched industrial Ethernet in the system menu.
- Backup / Restore
When replacing a sensor, if a sensor of the same model is connected to the same terminal position, the settings before the replacement are automatically written.
No sensor reconfiguration is required, which saves downtime.
- Users want real ease of use
OPTEX FA's IO-Link Master is equipped with an OLED display and operation keys that allow users to check, set, and change IO-Link device parameters, maintenance information, and errors without using a PC or HMI.
- Accurate data collection
Since IO-Link handles sensor measurement values as digital signals, there is no change in values due to noise, and the measured values can be accurately collected.
- Easy setup
Parameter settings for IO-Link pressure and flow sensors can be set from a host on the network. This reduces the possibility of sensor setting errors or unintentional setting omissions. The parameters once set can be backed up to the UR Series IO-Link master. If the sensor is replaced with one of the same model, the setting information can be restored to avoid accidentally different information than before.
- Miswire / Wire Break Detection
Any point that differs from the preconfigured connection information will be detected as a miswire. Even if power to an IO-Link device (sensor) is cut off due to a wire break, the determination signal of the sensor is maintained without interruption, and the wire break can be detected.
- Multi-point / Distributed I/O Control
In addition to IO-Link type devices, sink (NPN) and source (PNP) input/output devices can be connected to the IO-Link master, enabling effective use of remaining channels other than IO-Link type devices connection.
- IO-Link Master General Specifications
Model | UR-MS16DT | UR-ES16DT | |
---|---|---|---|
Supply voltage | 24 VDC +/-15 %*1 | ||
Current consumption | 195 mA | ||
Insulation resistance | 5 M ohm or more (between external power supply and unit power supply at 500 VDC) |
||
Input / Output common | Sink / Source switchable per channel | ||
Connectors | Field network: 2 x RJ45 socket Power supply: spring clamp terminal block, 5 positions x 2 rows Input / Output: 3 x 16-channel spring clamp terminal blocks |
||
Indicators | POWER LED (green), EVENT LED (yellow), ALARM LED (red), I/O LED (orange) |
||
Display | OLED Menu language: English, French, German, Italian, Japanese, Korean, Portuguese, Simplified Chinese, Spanish, Traditional Chinese |
||
Environmental resistance | Operating temp. / humidity | 0 to +55°C/5 to 95 % RH (no freezing or condensation)*2 | |
Storage temp. / humidity | -25 to +75°C/5 to 95 % RH (no freezing or condensation) | ||
Vibration resistance | IEC 61131-2 compliant | ||
Shock resistance | IEC 61131-2 compliant | ||
Operating atmosphere | No corrosive gas | ||
Operating altitude | 0 to 2000 m | ||
Installation location | Indoor use | ||
Degree of protection | IP20 (Not UL Certified) | ||
Overvoltage category | II or less | ||
Pollution degree | 2 or less | ||
Device class | Class Ⅰ | ||
Applicable regulations | EMC | EMC Directive (2014/30/EU) | |
Environment | RoHS Directive (2011/65/EU), China RoHS (Regulation32) | ||
Applicable standard | EN 61131-2 | ||
NRTL certification | UL Listed Programmable Controllers Certified for US and Canada | ||
Company standards | Noise resistance: Feilen Level 3 cleared | ||
Compatible DIN rail | TH35-7.5Fe, TH35-7.5Al | ||
Compatible wire | Power terminal block: AWG 24 to 16, I/O terminal block: AWG 28 to 16 | ||
Material | Housing: PC, Keys and DIN rail mounting hook: POM, Terminal block: PA | ||
Weight | Approx. 195 g (including terminal blocks, when not wired) | ||
Included accessories | Instruction manual, 3 x I/O terminal blocks, 1 x Power terminal block, 2 x Protective caps for RJ45 connector (attached to the unit) |
Model | UR-MS16DT | UR-ES16DT | |
---|---|---|---|
Input Specifications | Rated input voltage | 24 VDC +/-20%*1 | |
Rated input current (typical) | Source(PNP): 5.5 mA, Sink(NPN): 5.0 mA | ||
Insulation method | Transformer, photocoupler insulation | ||
Maximum number of simultaneous input points | 100 % simultaneous ON | ||
Voltage and current at ON | Source(PNP): 15 VDC or higher, 5.5 mA or higher, Sink(NPN): 13 VDC or higher, 3.0 mA or higher Note: Sink(NPN) is the voltage seen from the 24 V side. |
||
Voltage and current at OFF | Source(PNP): 10 VDC or less, 2.0 mA or less, Sink(NPN): 8 VDC or less, 2.0 mA or less Note: Source(NPN) is the voltage seen from the 24 V side. |
||
Input resistance | Source(PNP): 5.5 mA with constant current circuit load, Sink(NPN): 4.7 k ohm |
||
Input response time | 0 ms, 0.1 ms, 1 ms, 5 ms, 10 ms, 20 ms (default: 0 ms) |
Model | UR-MS16DT | UR-ES16DT | |
---|---|---|---|
Output Specifications | Rated load voltage | 10.8 to 26.4 VDC *1 | |
Maximum output load current | 0.2 A per 1 point, 2.5 A per 16 points *2 | ||
Maximum inrush current | Current limitation by over-current protection function (0.5 A) | ||
OFF output leakage current | 0.1 mA or less (0.2 mA or less for Sink NPN output) | ||
Maximum output voltage drop at ON |
Source(PNP): 1.8 V, Sink(NPN): 1.6 V | ||
Surge suppressor | Zener diode | ||
Output response time | 0.1 ms or less |
*1. Use a Class 2 power supply or a power supply compliant with SELV (Safety Extra-Low Voltage) circuit and LIM (Limited Energy Circuit) circuit standards.
*2. UL Satisfaction Ratings: I/O output load current is 2 A or less for a total of 16 channels at 0 to +55°C or 2.5 A or less for a total of 16 channels at 0 to +50°C
●Specifications and other information are subject to change without prior notice.
- IO-Link Specifications
Model | UR-MS16DT | UR-ES16DT | |
---|---|---|---|
IO-Link communication | IO-Link revision | 1.1 and 1.0 | |
Communication speed | COM1: 4800 bps, COM2: 38400 bps, COM3: 230.4 kbps | ||
Physical layer | IO-Link compliant | ||
Minimum cycle time | 0.3 ms | ||
Number of ports | 16 | ||
I/O assignment | Switchable in the following 6 modes by setting for each channel: • Disable mode • IO-Link communication mode • SIO (Digital Source PNP input) mode • SIO (Digital Sink NPN input) mode • SIO (Digital Source PNP output) mode • SIO (Digital Sink NPN output) mode |
||
Input related | Source(PNP) / Sink(NPN) channel switchable type | ||
Functions | Basic IO-Link communication | Cyclic communication, acyclic communication, event communication |
Process I/O communication, ISDU communication, event communication |
- Host Network Communication Specifications
Model | UR-MS16DT | UR-ES16DT |
---|---|---|
Communication method | CC-Link IE Field or CC-Link IE TSN (switchable in the master parameter) |
EtherNet/IP (default value), Ethernet & Modbus/TCP, CC-Link IE Field Basic, EtherCAT (switchable in the master parameter) |
Station type | Remote device station | See following table |
Transmission speed | 1 Gbps | |
Total cable extension | Between Field Network master station and this product: 100 m Between this product (IO-Link Master) and IO-Link devices: 20 m |
|
Station number setting | 1 to 120 (CC-Link IE Field) 1 to 254 (CC-Link IE TSN) |
- When the network type is "EtherNet/IP"
Item | Specifications |
---|---|
Host network communication protocol | EtherNet/IP |
Applicable version | EtherNet/IP adapter |
Transmission speed | 10M (10BASE-T)、100Mbps (100BASE-TX) |
Cable | Twisted pair cable (STP) Category 5, 5e or higher |
Ethernet connection type | Star configuration, linear bus configuration, device level ring configuration |
Distance between nodes | Within 100 m |
IP address setting | Static IP address |
- When the network type is "Ethernet & Modbus/TCP"
Item | Specifications |
---|---|
Host network communication protocol | Modbus/TCP communication or Ethernet socket communication |
Transmission speed | 10M (10BASE-T)、100Mbps (100BASE-TX) |
Cable | Twisted pair cable (STP) Category 5, 5e or higher |
Ethernet connection type | Star configuration, linear bus configuration |
- When the network type is "CC-Link IE Field Basic"
Item | Specifications |
---|---|
Host network communication protocol | CC-Link IE Field Basic communication, socket communication |
Transmission speed | 100 Mbps (100 BASE-TX) |
Cable | Twisted pair cable (STP) Category 5, 5e or higher |
Ethernet connection type | Star configuration, linear bus configuration |
- When the network type is "EtherCAT"
Item | Specifications |
---|---|
Transmission speed | 10 Mbps (10 BASE-T), 100 Mbps (100 BASE-TX) |
IP address setting | Static IP address |